Gx
Series
EN - 97
10 In case of
negative
result of the
NoTrip
(
Z
L-N
and/or
Z
L-PE
>199
), the auto test is automatically blocked, the
symbol is shown and the screen to the side is
displayed. Note red value of the relative Loop
impedance
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1)
11 In case of
negative
result of the
RCDX1
, the auto test
is automatically blocked, the
symbol is shown and
the screen to the side is displayed. Note red value of
the tripping time
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1)
12 In case of
negative
result of the
RCD
, the auto test is
automatically blocked, the
symbol is shown and
the screen to the side is displayed. Note red value of
the tripping current
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1)
13 In case of
negative
result of the
M
L-PE
, the auto test
is automatically blocked, the
symbol is shown and
the screen to the side is displayed. Note red value
(lower than minimum set trhreshold) of the L-PE
insulation resistance
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1)
14 In case of
negative
result of the
M
N-PE
, the auto
test is automatically blocked, the
symbol is shown
and the screen to the side is displayed. Note red
value (lower than minimum set trhreshold) of the N-PE
insulation resistance
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1)