Gx
Series
EN - 117
44
If the test fails, the screen like the one on the side is
shown on the display. The incorrect value of the
parameter is shown in red and the symbol
indicates
the non-ok result of the measurement
.
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test and to
end the test sequence
.
The instrument shows the message shown in the
followed screen for a few seconds
45 Repeat the sequence again if necessary
Test 4
Overall earth resistance measurement of the EVSE system
TT systems
46
Connect the instrument to the adapter as shown in the
diagram on the display (input
B4
on input
N,
input
B3
on input
E
and input
B1
on input
L1
)
.
Act on the three
adapter selectors by setting the followed positions
as shown by the instrument by flashing red/blue
indications
:
PP State
13A,20A,32A or 63A
CP State
C
Fault
OK
Press the icon
to continue with the test or press the
icon
to exit the test and return to the initial screen
47
The test is performed by the instrument
only in
"NoTrip " mode
. Refer to
§ 6.4.12
for the description
on the setting of the test parameters relative to the trip
out current of the RCD,
absence of neutral conductor
(only possible measurement
) and the preliminary
calibration of the measuring terminals
Press the
GO/STOP key for a few seconds
. The
followed screen is shown on the display