Gx
Series
EN - 111
20
Connect the instrument to the adapter as shown in the
diagram on the display (input
B4
on input
N,
input
B3
on input
E
and input
B1
on input
L1
).
Act on the three adapter selectors by setting the
followed positions as shown by the instrument by
flashing red/blue indications
:
PP State
NC
CP State
A
Fault
OK
Press the icon
to continue with the test or press the
icon
to exit the test and return to the initial screen
21
The result of the measurement is shown in the screen
to the side
. The symbol
indicates the correct result
of the measurement.
The symbol
also indicates a
positive result of the measurement but with values
outside the limits present in the Table 4.
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the
icon for the
partial saving of the test and continue with the next test
(point 24)
22
If the test fails, the screen like the one on the side is
shown on the display. The incorrect value of the
parameter is shown in red and the symbol
indicates
the non-ok result of the measurement
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test and to
end the test sequence
.
The instrument shows the message shown in the
followed screen for a few seconds
23 Repeat the sequence again if necessary