Test 2
Insulation measurement of EVSE system
10
Connect the instrument to the adapter as shown in the
screen on the display (input
B4
on input
N
, input B3 on
input
E
and input
B1
on input
L1
)
Act on the three adapter selectors by setting the
followed positions as shown by the instrument by
flashing red/blue indications
:
PP State
NC
CP State
A
Fault
OK
Press the icon
to continue with the test or press the
icon
to exit the test and return to the initial screen
11
The test is performed by the instrument
only in AUTO
L/N-PE mode
. Refer to § 6.2.2 for the description on
setting of test parameters
Press the
GO/STOP
button. The followed screen is
shown on the display
12
For single-phase EVSE systems
, the measurement
result is shown in the screen to the side. The values of
the real test voltages are shown on the display
. The
symbol
indicates the correct result of the
measurement.
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the
icon for the
partial saving of the test and continue with the next test
(point 20)
13
For three-phase EVSE systems
, the measurement
result of the
first L1PE test
is shown in the screen to
the side. The values of the real test voltages are shown
on the display
The symbol
indicates the correct result of the
measurement.
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the
icon for the
partial saving of the test and continue with the next test
on L2 phase. The followed screen is shown on the
display