Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
-58-
HD3Z Series User Manual V1.2
Ref. Code
Function Description
Setting Range [Default]
F19.35
Aux PID output limit
0.0 - 100.0 [100.0%]
When aux frequency selects PID, adjustment upper limit of PID output = F19.35 × main setting frequency.
F19.36
Aux PID output setting
0.0 - 100.0 [0.0%]
Aux PID output setting = output llimit of F19.35 + F19.36 × F00.06.
F19.37
Frequency adjustment range
000 - 111 [100]
Unit: Main frequency calculating range
•
0: 0 - max. frequency.
•
1: Negative max. frequency - max. frequency.
Ten: Aux frequency calculating range
•
0: 0 - max. frequency.
•
1: Negative max. frequency - max. frequency.
Hundred: Resultant frequency calculating range
•
0: 0 - upper limit frequency.
•
1: Negative upper limit frequency - upper limit
frequency.
F19.38
Inter-phase short-circuit detection
0,1 [1]
Used to detect inter-phase short-circuit before running HD3Z.
0: Do not detect.
1: Detect.
F19.39
Input voltage selection
0 - 2 [1]
0: 380 - 460V.
1: 260 - 460V.
2: 200 - 460V.
Note : When F19.39 = 1 or 2, HD3Z needs derating to use, and the actual output current should not surpass rated
output current of HD3Z.
F19.40
Flux braking PI regulator Kp
0 - 4000 [1000]
F19.41
Flux braking PI regulator Ki
0 - 500 [20]
F19.42
Motor dehumidifying current
1 - 80 [10%]
F19.43
Dehumidifying time when current of motor rises
0.1 - 240.0 [30.0min]
F19.44
Motor auto dehumidification selection
0x00 - 0x11 [0x11]
Ten: The basis of judgement for starting the auto dehumidification
of the motor
•
0: According to humidity.
•
Before each operation, the inverter detects the motor humidity
value (d00.53). When the motor humidity value (d00.53) >
F19.45 and the terminal automatic dehumidification is effective,
the motor starts with the dehumidification current value curve
according to the right figure before it runs.
•
1: According to the stop interval.
•
Before each operation, the inverter detects the interval time of this operation and last opereation
(d01.07), when the stop interval (d01.07) ≥ F19.48 (F19.48 is not zero) and the terminal automatic
dehumidification is effective, the motor starts dehumidification according to the dehumidification
current value curve on the right before it runs.
Unit: The judgement basis for stopping automatic dehumidification of the motor
•
0: According to humidity.
•
After the motor starts to dehumidify automatically, when the motor humidity value (d00.53) < (F16.45 -
F19.46), the motor dehumidification process ends and the motor starts normally.
•
1: According to time.
•
After the motor starts to dehumidify automatically, after the F19.47 time, the dehumidification process
ends and the motor starts normally.
Dehumidifying current (%)
Dehumidifying time
F19.42
0
F19.43