Appendix B Parameters
Shenzhen Hpmont Technology Co., Ltd.
-86-
HD3Z Series User Manual V1.2
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F04.13
PID regulator upper limit
0.0 - 100.0%
100.0%
0.1%
×
F04.14
PID regulator lower limit
0.0 - 100.0%
0.0%
0.1%
×
F04.15
Regulating characteristic
of PID regulator
0: Positive characteristic
1: Negative characteristic
0
1
×
F04.17
PID output filtering time
0.01 - 10.00s
0.05s
0.01s
○
F04.18
REV selection when PID
outputs
0: Prohibit REV when PID regulates
1: Permit REV
0
1
×
F04.19
REV frequency upper limit
of PID output
0.0 - 100.0%
100.0%
0.1%
×
F04.20
Proportional gain (P2)
0.0 - 100.0
50.0
0.1
○
F04.21
Integral time (I2)
0.01 - 10.00s
1.00s
0.01s
○
F04.22
Differential time (D2)
0.00 - 10.00s
0.00s
0.01s
○
F04.23
PID parameter adjustment
bases
0: Do not adjust
1: DI
2: Bias
3: Frequency
0
1
○
F04.24
PID parameter switching
point 1
0.0% - F04.25
0.0%
0.1%
○
F04.25
PID parameter switching
point 2
F04.24 - 100.0%
100.0%
0.1%
○
F04.29
PID calculating mode
0: Do not calculate when HD3Z
stops
1: Calculate when HD3Z stops
0
1
○
F04.30
PID dormancy selection
0: Disable
1: Enable
0
1
○
F04.31
Wakeup tolerance
0.0 - 100.0%
10.0%
0.1%
○
F04.32
Wakeup delay
0.0 - 6000.0s
0.0s
0.1s
○
F04.33
Dormancy tolerance
0.0 - 100.0%
10.0%
0.1%
○
F04.34
Dormancy delay
0.0 - 6000.0s
0.0s
0.1s
○
F04.35
Dormancy frequency
0.00Hz - Max. frequency
20.00Hz
0.01Hz
○
F05: External Setting Curve Parameter
F05.00
External setting curve
selection
Unit: AI1 curve
Ten: AI2 curve
Ten thousand: Pulse curve
0: Line 1
1: Line 2
2: Polyline
3: Do not dispose
33333
1
○
F05.01
Line 1 min. setting
0.0% - F05.03
0.0%
0.1%
○
F05.02
Corresponding value of
line 1 min. setting
0.0 - 100.0%
0.0%
0.1%
○
F05.03
Line 1 max. setting
F05.01 - 100.0%
100.0%
0.1%
○
F05.04
Corresponding value of
0.0 - 100.0%
100.0%
0.1%
○