Shenzhen Hpmont Technology Co., Ltd.
Appendix B Parameters
HD3Z Series User Manual V1.2
-99-
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
protection
3: Shield inverter overload
protection and motor overload
protection
F20.01
Overload pre-alarm
detection value
20.0 - 200.0%
150.0%
0.1%
×
F20.02
Overload pre-alarm
detection time
0.0 - 60.0s
5.0s
0.1s
×
F20.08
The detection base of lack
of input
0 - 80%
0: Not detect input phase loss fault
30%
1%
×
F20.09
The detection time of lack
of input
1.00 - 5.00s
1.00s
0.01s
×
F20.10
The detection base of lack
of output
0 - 100%
0: Not detect output phase loss fault
20%
1%
×
F20.11
The detection time of lack
of output
1.00 - 20.00s
3.00s
0.01s
×
F20.12
PID setting lose detection
value
0 - 100%
0: Not detect PID setting loss fault
0%
1%
×
F20.13
PID setting loss detection
time
0.00 - 10.00s
0.00: Not detect PID setting loss fault
0.20s
0.01s
×
F20.14
PID feedback loss
detection value
0 - 100%
0: Not detect PID feedback loss fault
0%
1%
×
F20.15
PID feedback loss
detection time
0.00 - 10.00s
0.00: Not detect PID feedback loss fault
0.20s
0.01s
×
F20.16
Detection value at PID
feedback out of the limit
0 - 100%
100: Not detect PID feedback out of
limit fault
100%
1%
×
F20.17
Detection time at PID
feedback out of the limit
0.00 - 10.00s
0.00: Not detect PID feedback out of
limit fault
0.20s
0.01s
×
F20.18
Fault auto reset times
0 - 100
0: Auto reset is unused
0
1
×
F20.19
Fault auto reset interval
0.01 - 200.00s/time
5.00s/
time
0.01s/
time
×
F20.20
Faulty relay action
Unit: In auto reset process
0: Faulty relay doesn’t act
1: Faulty relay acts
Ten: In undervoltage process
0: Faulty relay doesn’t act
1: Faulty relay acts
00
1
○
F20.21
NO.5 fault type
-Lu-: DC bus undervoltage
E0001: Inverter output overcurrent
E0002: Inverter output overcurrent
E0003 Inverter output overcurrent
0
1
*
F20.21
NO.5 fault type
E0004: DC bus over voltage (in Acc.
0
1
*
B