Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
-26-
HD3Z Series User Manual V1.2
Ref. Code
Function Description
Setting Range [Default]
d00.24
Output power (kW)
[Actual value]
d00.25
DC busbar voltage (V)
[Actual value]
d00.27
AI1 input (%)
[Actual value]
d00.28
AI1 input (after calculating) (%)
[Actual value]
d00.29
AI2 input (%)
[Actual value]
d00.30
AI2 input (after calculating) (%)
[Actual value]
d00.35
DI6 terminal pulse input frequency (Hz)
[Actual value]
d00.36
AO1 output (%)
[Actual value]
AO1 is voltage output, 0.0% corresponds to 0V, 100.0% corresponds to 10V.
d00.37
AO2 output (%)
[Actual value]
AO2 is current output, 0.0% corresponds to 0mA, 100.0% corresponds to 20mA.
d00.39
Heatsink temperature (°C)
[Actual value]
d00.42
Ambient humidity (%rm)
[Actual value]
d00.43
Ambient temperature (°C)
[Actual value]
d00.44
PID setting (%)
[Actual value]
Display PID setting relative to full scale percentage.
d00.45
PID feedback (%)
[Actual value]
Display PID feedback relative to full scale percentage.
d00.46
PID tolerance (%)
[Actual value]
Display PID tolerance relative to full scale percentage.
d00.47
PID integral item (%)
[Actual value]
Display PID integral item tolerance relative to percentage of max. output frequency.
d00.48
PID output (%)
[Actual value]
Display PID output relative to percentage of max. output frequency.
d00.50
Input terminal status
[Actual value]
Display input terminal status. Each bit (binary) of this parameter stands for different physical channels
which are in below table.
•
0: Input terminals disconnect with common terminals.
•
1: Input terminals connect with common terminals.
123Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
-
-
DI6
DI5
DI4
DI3
DI2
DI1
123
d00.51
Output terminal status
[Actual value]
Display output terminal status. Each bit (binary) of this parameter stands for different physical channels
which are in the below table.
•
0: Output terminals disconnect with common terminals.
•
1: Output terminals connect with common terminals.
Bit11 Bit10
Bit9
Bit8
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
-
-
-
RLY7
RLY6
RLY5
RLY4
RLY3
RLY2
RLY1 Unused DO1
123
d00.52
MODBUS communication status
[Actual value]
Display MODBUS communication status.
0: Normal.
1: Communication timeout.
2: Wrong data frame head.
4: Wrong data frame content.