Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
-50-
HD3Z Series User Manual V1.2
Ref. Code
Function Description
Setting Range [Default]
F15.30
FDT1 detection mode
0,1 [0]
0: Detect according to setting frequency.
1: Detect according to output frequency.
F15.31
FDT1 level
0.00 - Upper limit frequency
[50.00Hz]
F15.32
FDT1 delay
0.00 - Upper limit frequency
[1.00Hz]
When F15.30 > F15.31, HD3Z outputs command signal until
output frequency is lower than FDT1 level and delay (FL)
(F15.31 - F15.32).
F15.33
FDT2 detection mode
0,1 [0]
0: Detect according to setting frequency.
1: Detect according to output frequency.
F15.34
FDT2 level
0.00 - Upper limit frequency
[50.00Hz]
F15.35
FDT2 delay
0.00 - Upper limit frequency
[1.00Hz]
Refer to F15.31 and F15.32.
F15.39
Action selection when motor is overheated
00 - 30 [00]
If corresponding analogue temperature of motor > F15.40 or analogue < F15.41 and go through F15.42,
HD3Z report motor overheat fault, motor coast to stop.
Ten: Select analogue input terminal
•
0: No analogue terminal.
•
2: AI1.
•
3: AI2.
F15.40
Upper limit of motor overheat input
0.0 - 100.0 [100.0%]
F15.42
Detection time of motor overheat
0.00 - 50.00 [5.00s]
F15.43
Terminal output delay
0.0 - 100.0 [0.0s]
F15.45
RLY5 relay function
0 - 41 [0]
F15.46
RLY6 relay function
0 - 41 [0]
F15.47
RLY7 relay function
0 - 41 [0]
Function of F15.45 - F15.47 are the same as F15.20 - F15.23 (Relay RLY1 - RLY4).
Output frequency
F15.32
F15.31
FL
Time
Time
DO