Shenzhen Hpmont Technology Co., Ltd.
Appendix B Parameters
HD3Z Series User Manual V1.2
-97-
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F19.21
Auto current limit
threshold
20.0 - 200.0%
120.0%
0.1%
×
F19.23
Enabled terminal at power
on
0: Rise edge
1: Level
0
1
○
F19.25
Flux braking
0: Disabled
1: Enable
0
1
×
F19.35
Aux PID output limit
0.0 - 100.0%
100.0%
0.1%
○
F19.36
Aux PID output setting
0.0 - 100.0%
0.0%
0.1%
○
F19.37
Frequency adjustment
range
Unit: Main frequency calculating
range
0: 0 - max. frequency
1: Negative max. frequency- max.
frequency
Ten: Aux frequency calculating range
0: 0 - max. frequency
1: Negative max. frequency- max.
frequency
Hundred: Resultant frequency
calculating range
0: 0 - upper limit frequency
1: Negative upper limit frequency -
upper limit frequency
100
1
○
F19.38
Inter-phase short-circuit
detection
0: Do not detect
1: Detect
1
1
○
F19.39
Input voltage selection
0: 380 - 460V
1: 260 - 460V
2: 200 - 460V
1
1
×
F19.40
Flux braking PI regulator
Kp
0 - 4000
1000
1
○
F19.41
Flux braking PI regulator
Ki
0 - 500
20
1
○
F19.42
Motor dehumidifying
current
1 - 80%
10%
1%
×
F19.43
Dehumidifying time when
current of motor rises
0.1 - 240.0min
30.0min
0.1min
○
F19.44
Auto dehumidifying
selection
Ten: The basis of judgement for
starting the auto dehumidification of
the motor
0: According to humidity
1: According to the stop interval
0
1
×
B