Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3Z Series User Manual V1.2
-25-
Chapter 6
Function Introduction
6.1
Display Parameter
Group d is status display parameter.
6.1.1
d00: Status Display Parameter
Ref. Code
Function Description
Setting Range [Default]
d00.00
HD3Z series
[Actual value]
d00.01
Software version of HD3Z
[Actual value]
d00.03
Non-standard software version of HD3Z
[Actual value]
d00.05
Software version of keypad
[Actual value]
d00.06
Customized serial number
[Actual value]
d00.08
Rated current of HD3Z (A)
[Actual value]
d00.10
Inverter status
[Actual value]
Displays the inverter status, as following:
Thousand
Bit15: Frequency
switch mode
0: Not timing
1: Timing
Bit14: Timing start /
stop mode
0: Not timing
1: Timing
Bit13: Auto current
restriction
0: Do not restrict
1: Restrict
Bit12: Stall
overvoltage
0: Invalid
1: Valid
Hundred
Bit11: Dehumidifing
status of motor
0: Not started
1: Under way
Bit10: Speed limitation
0: Below limitation
1: Above limitation
Bit9: Unused
Bit8: Unused
Ten
Bit7: DC brake
0: Invalid
1: Valid
Bit6: Unused
Bit5&Bit4: Acc. / Dec. / Constant
00: Constant
11: Constant
01: Acc.
10: Dec.
Unit
Bit3: Zero speed
0: Invalid
1: Valid
Bit2: Forward / Reverse
0: Forward
1: Reverse
Bit1: Run / Stop
0: Stop
1: Run
Bit0: Inverter fault
0: Normal
1: Faulty
123
d00.11
Main setting frequency channel
[Actual value]
0: Keypad.
1: Terminal.
2: Communication.
3: Analogue.
4: Terminal pulse.
6: AI1.
7: AI2.
11: PID.
12: Multi-speed.
14: Timing frequency.
d00.12
Main setting frequency (Hz)
[Actual value]
d00.13
Aux setting frequency (Hz)
[Actual value]
d00.14
Setting frequency (Hz)
[Actual value]
d00.15
Setting frequency (after Acc. / Dec.) (Hz)
[Actual value]
d00.16
Output frequency (Hz)
[Actual value]
d00.17
Setting rpm (rpm)
[Actual value]
d00.18
Running rpm (rpm)
[Actual value]
d00.20
Output voltage (V)
[Actual value]
d00.21
Output current (A)
[Actual value]
d00.23
Output torque (%)
[Actual value]
6