Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3Z Series User Manual V1.2
-51-
6.2.13
F16: Analogue I/O Terminal Parameters
Ref. Code
Function Description
Setting Range [Default]
F16.01
AI1 function
0 - 23 [2]
F16.02
AI2 function
0 - 23 [0]
0: Unused.
2: Frequency setting.
•
F00.10 = 3 (analogue input sets frequency setting channel), setting frequency is set by corresponding
input voltage.
3: Aux frequency setting.
•
F19.00 = 4 (analogue sets aux frequency setting), aux frequency is set by corresponding input voltage.
4: Process PID setting.
•
F04.01 = 1 (analogue sets process PID setting), process PID setting is set by corresponding input
voltage.
5: Process PID feedback.
•
F04.02 = 0 (analogue inputs process PID feedback), process PID feedback is set by corresponding input
voltage.
6: Process PID regulating upper limit.
•
F04.11 = 1 (analogue sets upper limit of PID regulator), process PID regulating upper limit is set by
corresponding input voltage.
7: Process PID regulating lower limit.
•
F04.12 = 1 (analogue sets lower limit of PID regulator), process PID regulating lower limit is set by
corresponding input voltage.
20: Detect ambient humidity.
21: Detect ambient temperature.
22: Detect motor humidity.
23: Detect motor temperature.
F16.05
AI1 bias
-100.0 - 100.0 [0.0%]
F16.08
AI2 bias
F16.06
AI1 gain
0.00 - 10.00 [1.00]
F16.09
AI2 gain
F16.07
AI1 filtering time
0.01 - 10.00 [0.05s]
F16.10
AI2 filtering time
When AI1 - AI2 is open loop frequency setting channel, the relationship between the analogue input and
the analogue value after calculating is shown as figure:
The formula is: Y=kX+b.
•
Y is analogue after calculating, X is value before adjusting, k is analogue input gain (F16.06, F16.09), b is
analogue input bias (F16.05, F16.08).
F16.17
Max. input pulse frequency
0 - 50000 [10000Hz]
When set the DI6 as pulse input, F16.17 defines the max. input pulse frequency.
F16.18
Input pulse filter time
0.01 - 10.00 [0.20s]
Analogue
actual value
Analogue
input filtering
Analogue input gain
Analogue input bias
Analogue value
after calculating
AI display value
AI display value
(after calculating)
6