Appendix B Parameters
Shenzhen Hpmont Technology Co., Ltd.
-98-
HD3Z Series User Manual V1.2
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
Unit: The judgement basis for
stopping automatic
dehumidification of the motor
0: According to humidity
1: According to time
F19.45
Motor auto dehumidifying
humidity
F19.46 - 100.0%rm
80.0% rm
0.1% rm
○
F19.46
Motor auto dehumidifying
humidity delay
0.0 - 30.0%rm
5.0% rm
0.1% rm
○
F19.47
Motor auto dehumidifying
humidity time
0.1 - 1200.0min
120.0min
0.1min
○
F19.48
Motor auto
dehumidification stop
interval
0.0 - 6000.0h
0.0h
0.1h
×
F20: Fault Protection Parameters (on pages 59 - 61)
F20.00
Overload pre-alarm
detection
Unit: Overload pre-alarm detection
0: It is active all the time in running
status
1: It is active only at constant speed
Ten: Overload pre-alarm action
0: HD3Z doesn’t alarm and continues
running when detecting an active
overload signal
1: HD3Z alarms and stops running
when detecting an active overload
signal
Hundred: Overload detection
threshold
0: Relates to rated current of motor
(alarm E0019: Motor overload)
1: Relates to rated current of HD3Z
(alarm E0017: Inverter overload)
Thousand: Motor type
0: Standard motor
1: Variable frequency motor
Ten thousand: Overload protection
0: Enable inverter overload
protection and motor overload
protection
1: Enable inverter overload
protection; Shield motor overload
protection
2: Shield inverter overload
protection; Enable motor overload
00000
1
×