Appendix B Parameters
Shenzhen Hpmont Technology Co., Ltd.
-94-
HD3Z Series User Manual V1.2
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F17.04
Detection time at
communication timeout
0.0 - 600.0s
0.0: Not detect communication
timeout
0.0s
0.1s
×
F17.05
Detection time at
communication error
0.0 - 600.0s
0.0: Not detect the communication
error
0.0s
0.1s
×
F17.06
Action selection at
communication timeout
0: Coast to stop
1: Emergency stop
2: Decelerate to stop
3: Continue to run
3
1
×
F17.07
Action selection at
communication error
3
1
×
F17.08
Action selection at
communication peripheral
device fault
1
1
×
F17.09
EEPROM storage selection
under communication
read / write function
parameter
Unit: Parameters storage selection
except F00.13 and F19.03
Ten: F00.13 and F19.03 storage
selection
0: Do not store to EEPROM
1: Store to EEPROM
F17.09 is used to select parameter
storage during modifying
01
1
×
F17.10
Detection time of
networking
communication timeout
0.0 - 600.0s
0.0s
0.1s
×
F18: Display Control Parameter (on pages 54 - 55)
F18.01
Display contrast of LCD
keypad
1 - 10
5
1
○
F18.02
Set parameter 1 of run
status
0: Unused
1: Rated current of HD3Z
3: Invertre status
4: Main setting frequency channel
5: Main setting frequency
6: Aux setting frequency
7: Setting frequency
8: Setting frequency (after Acc. /
Dec.)
9: Output frequency
10: Setting Rpm
11: Running Rpm
13: Output voltage
14: Output current
16: Output torque
17: Output power
18: DC busbar voltage
20: AI1 input voltage
9
1
○
F18.03
Set parameter 2 of run
status
7
1
○
F18.04
Set parameter 3 of run
status
13
1
○
F18.05
Set parameter 4 of run
status
14
1
○
F18.06
Set parameter 5 of run
status
35
1
○
F18.07
Set parameter 6 of run
status
36
1
○