Appendix B Parameters
Shenzhen Hpmont Technology Co., Ltd.
-96-
HD3Z Series User Manual V1.2
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F19.02
Aux setting coefficient
0.00 - 9.99
1.00
0.01
○
F19.03
Initial value of digital aux
frequency
0.00 - F00.06
0.00Hz
0.01Hz
○
F19.04
Digital aux frequency
control
Unit: Storage selection at power
failure
0: Do not save aux frequency
1: Save aux frequency
Ten: Frequency at stop
0: Maintain aux frequency at stop
1: Aux frequency resumes to F19.03
at stop
00
1
○
F19.05
Setting frequency
adjustment selection
0: Do not adjust
1: Adjust according to max. output
frequency (F00.06)
2: Adjust according to current
frequency
1
1
○
F19.06
Setting frequency
adjustment coefficient
0.0 - 200.0%
100.0%
0.1%
○
F19.07
Fan control
0: Auto stop
1: Immediate stop
2: Runs all the time when power on
0
1
○
F19.08
Fan control delay time
0.0 - 600.0s
120.0s
0.1s
○
F19.10
Zero frequency threshold
0.00Hz - Upper limit frequency
1.00Hz
0.01Hz
○
F19.11
Action selection when
setting frequency < zero
frequency threshold
0: Runs according to frequency
command
1: Remains stop and does not output
2: Runs according to zero frequency
3: Runs at 0Hz
0
1
×
F19.12
Non-stop at instantaneous
power loss
0: Forbid non-stop at instantaneous
power loss
1: Enable non-stop at instantaneous
power loss
0
1
×
F19.13
Voltage compensation
gain for non-stop running
10 - 1000
500
1
○
F19.15
Voltage for action
judgement at
instantaneous power loss
340 - 670V
430V
1V
×
F19.16
Restart after power failure
0: Disabled
1: Enabled
0
1
×
F19.17
Waiting time for restart
after power failure
0.00 - 10.00s
2.00s
0.01s
○
F19.18
Overvoltage suppression
gain
0.000 - 1.000
0.000: Forbid stall overvoltage
0.000
0.001
○
F19.19
Stall overvoltage point
650 - 790V
690V
1V
×
F19.20
Auto current limit gain
0.000 - 1.000
0.500
0.001
○