Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
-48-
HD3Z Series User Manual V1.2
Ref. Code
Function Description
Setting Range [Default]
F15.17
Action selection when extrenal device has fault
0 - 3 [0]
Protection action when external device has fault.
0: Coast to stop.
1: Emergency stop.
2: Decelerate to stop.
3: Continue to run.
F15.18
DO1 function
0 - 41 [2]
F15.20
RLY1 relay function
0 - 41 [31]
F15.21
RLY2 relay function
0 - 41 [0]
F15.22
RLY3 relay function
0 - 41 [0]
F15.23
RLY4 relay function
0 - 41 [0]
0: Unused.
1: Inverter is ready.
•
Inverter can output normal running command after power up, it’s enabled to run (DI = 1) and no fault
occurs.
2: Inverter running. HD3Z is in run status.
3: Forward running. HD3Z is forward running.
4: Reverse running. HD3Z is reverse running.
5: DC brake. HD3Z is DC brake.
6: Zero-frequency status.
•
In zero-frequency range, the output frequency (including in stop status) outputs.
•
Refer to F15.28 and F15.29.
7: Zero-frequency running.
•
HD3Z output frequency is within zero-frequency range. Refer to F15.28 and F15.29.
9,10: Frequency level detection signal (FDT1, FDT2).
•
Refer to F15.31 - F15.35.
11: Frequency within FAR range (FAR).
•
The output frequency is within FAR range. Detection range is set by F15.27.
12: Frequency upper limit.
•
Indicating signal will output when setting frequency ≥ upper limit frequency.
13: Frequency lower limit.
•
Indicating signal will output when setting frequency ≤ lower limit frequency.
20: Signal output from SCI.
•
SCI control open collector output terminal or relay to output signal.
22: Timing function.
•
Output terminal of timing function. Refer to F15.25 and F15.26.
27: Analogue input exceeding limit.
•
When analogue exceeds upper or lower limit, output indicating signal.
•
Refer to F15.39 - F15.42.
COM
F15.16=2
F15.16=3
DIx
DIz
DIy
COM
DIx
DIz
DIy
SB2
SB2
SB3
K
SB1
SB1
FWD
FWD /REV
RUN
REV
SB1: Normally closed stop button
SB2: Normally open forward button
SB3: Normally open reverse button
K: Direction selection terminal (level on)
K = 0(forward) K = 1(reverse)
SB1: Normally closed stop button
SB2: Normally open run button
Three-wire
Three-wire