Figure 2-1 Airflow Through HP 9000 rp4410 and rp4440 Servers
Acoustic Noise Specification
The acoustic noise specification for the HP 9000 rp4410 or rp4440 server is 53 db LpA (sound
pressure level at bystander position in a dedicated computer room environment temperature of
<25°C).
Physical and Environmental Specifications
provides temperature and airflow information for minimum, typical, and maximum
configurations for the HP 9000 rp4410 and rp4440 servers. It also lists the server and rack weights
and dimensions.
Table 2-7 Physical and Environmental Specifications
Overall Server
(W x D x H)
Weight
Condition
Airflow, at
Maximum
Ambient degrees
C
1
Airflow, Nominal
Typical
Heat
Release
Pedestal
Rack
Pedestal
Rack
Server
Alone
180-264
VAC
W: 10.3 in
(26.1 cm)
D: 27.4 in
(69.5 cm)
H: 20.9 in
(53.0 cm)
W: 19 in
(48.2 cm)
D: 27.2 in
(69.0 cm)
H: 6.8 in
(17.3 cm)
115 lbs
(53 kg)
100 lbs
(45.4 kg)
88 lbs
(40 kg)
425
m3/hr
250
CFM
297
m3/hr
175 CFM
410 Watts
Min.
Config.
1368 Watts
Max.
Config.
1065 Watts
Typical
Config.
48
System Specifications