Table 2-2 Server Dimensions and Values
(continued)
Value
Dimension
Unloaded 88 lbs (40 kg)
Fully loaded 100 lbs (45.4 kg)
Weight
6.8 in (17.3 cm)
Height
Grounding
The site building must provide a safety ground or protective earth for each ac service entrance
to all cabinets.
Install a protective earthing (PE) conductor that is identical in size, insulation material, and
thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow
stripes. The earthing conductor is to be connected from the unit to the building installation earth
or, if supplied by a separately derived system, at the supply transformer or motor-generator set
grounding point.
Electrical Specifications
This section provides electrical specifications for the server.
AC Power Cords
lists the power cables available for use with the HP 9000 rp4410 and rp4440 servers.
Table 2-3 Power Cords
Country
Description
Part Number
South Africa
Power Cord C15/S Africa 2.5m black CA ASSY 917
8120-5341
United Kingdom
Hong Kong
Singapore
Power Cord C13/BS-1363 2.3m black CA ASSY 900
8120-1351
Australia
Power Cord C13/AS-3112 2.0m gray CA ASSY 901
8120-1369
Europe
Power Cord C13/CEE 7 2.0m black CA ASSY 902
8120-1689
Switzerland
Power Cord C13/SEV 12 2.0m black CA ASSY 906
8120-2104
Denmark
Power Cord OPT-912 3-COND 2.25-M-LG 912
8120-6814
North America (250#V)
Japan
Power Cord C13/6-15P 0.0m black CA ASSY 904 / 918
8120-0698
Israel
Power Cord OPT-919 3-COND 2.3-M-LG 919
8120-6800
Argentina
Power Cord C15/CEI 23-16 2.5m black CA ASSY 920
8120-8390
Chile
Power Cord C15/CEI 23-16 2.5m black CA ASSY 921
8120-8389
China
Power Cord C13/GB-1002 2.236m gray CA ASSY 922
8120-8376
South America
Power Cord OPT-927 3-COND 2.3-M-LG FLNT 927
8121-0668
All
C13/C14 Jumper cord
8120-6514
Circuit Breaker
The marked electrical size for the server is eight amps. The recommended circuit breaker size is
12 amps per line cord (2 maximum) for North America. For countries outside North America,
44
System Specifications