Appendix B
System Specifications
Temperature and Humidity Operating Standards
190
Temperature and Humidity Operating Standards
The following table lists the temperature and humidity specifications for rp54xx servers.
NOTE
Operating ranges refer to the ambient air temperature and humidity measured at the cabinet
cooling air intake vents.
Thermal Protection Features
If the cabinet temperature approaches 35
o
C, thermal protection will be invoked. At 35
o
C +/- 2
o
C a warning
message will be displayed on the system console. At 40
o
C +/- 2
o
C an ungraceful shutdown will occur.
Temperature and Humidity Specifications
Parameter
Operational
Limits
Recommended
Operating
Range
Maximum
Rate of Change
(per hour)
Non-Operating
Ranges
Temperature
a
a. The rp54xx has been designed to operate within the above specific temperature and relative
humidity operational limits. In general, operating any electronic equipment within the
recommended ranges of temperature and humidity will produce optimal reliability.
5
o
C to 35
o
C
(41
o
F to 95
o
F)
b
b. Temperature ranges stated above are at sea level. Maximum operating temperature is
derated (reduced) by 2
o
C for each 1000 meters above sea level up to a maximum of 3000
meters.
20
o
C to 25
o
C
(68
o
F to 77
o
F)
10
o
C (50
o
F) per
hour (With tape
media)
20
o
C (68
o
F) per
hour (Without
tape media)
-40
o
C to +70
o
C
(-40
o
F to +158
o
F)
Operating
Humidity
15 to 80%
Relative
humidity
(Non-condensing)
at 35
o
C (95
o
F)
40 to 60%
Relative
humidity
(Non-condensing)
30% Per hour
Relative humidity
(Non-condensing)
90% Relative
humidity
(Non-condensing)
at 65
o
C (149
o
F)
Summary of Contents for L1000 - 9000 - 0 MB RAM
Page 7: ...Contents vii Typical Installation Schedule 207 Site Inspection 208 Delivery Survey 212 ...
Page 8: ...Contents viii ...
Page 10: ...Tables x ...
Page 12: ...Figures xii ...
Page 14: ...xiv ...
Page 16: ...Chapter 1 Server Overview 2 ...
Page 17: ...Chapter 2 3 2 Server Unpacking and Installation ...
Page 37: ...Chapter 3 23 3 Installing Additional Components ...
Page 60: ...Chapter 3 Installing Additional Components Installing Disk Drives 46 ...
Page 61: ...Chapter 4 47 4 Cable Connections ...
Page 91: ...Chapter 5 77 5 Utilities ...
Page 98: ...Chapter 5 Utilities Configuring the Rev B Guardian Service Processor GSP 84 ...
Page 99: ...Chapter 6 85 6 Troubleshooting ...
Page 134: ...Chapter 6 Troubleshooting Fan Power Supply and Disk LED States 120 ...
Page 189: ...Appendix A 175 A Parts and Accessories ...