Cabling
Braid
Must have a minimum 65% coverage
Foil
When used with braid, provides 100% coverage.
Do not use foil alone. It has a tendency to break.
Stranded
Pair
Provides the greatest surface area
Shield
Termination
Continuation of the shield to the cabinet earth ground is most
important.
For discrete wire terminations, pigtails to the cabinet (connector)
ground should be extremely short (no greater than three inches).
For multiconductor connector terminations, only 360° shielded
shells should be used.
Note: Honeywell Analytics product testing uses >65% braid with foil (around the bundle); twisted
pair; stranded 24 AWG (minimum wiring for all qualification and certification testing.)
Vertex Edge System
8
User Manual