Stale CC Fault
When this option is ON and Chemcassette is nearing its expiration date, the maintenance fault
will be generated.
Accelerated CC Usage Fault
When this option is ON and Chemcassette usage for up to 24 hours exceeds twice of the average
daily usage, the maintenance fault will be generated.
Generate low CC fault
Vertex Edge software tracks the amount of Chemcassette® tape remaining on the supply reel
and triggers a low tape event when remaining tape is less than Days Before Due. Choosing OFF
disables the low tape event.
Set Timeout Values
Authorized users may temporarily disable points or inhibits alarms from activating and points
from monitoring. A point or alarm that is disabled/inhibited longer than the timeout limit will
cause a maintenance fault which will call attention to locations excluded from monitoring.
Select On and enter a timeout up to displayed minutes or select OFF to disable the maintenance
fault.
Vertex Edge System
54
User Manual
Summary of Contents for Vertex Edge
Page 1: ...Vertex Edge 72 POINT CONTINUOUS MONITOR ...
Page 2: ......
Page 6: ......
Page 19: ...Chemcassette 1 Chemcassette directional flow Vertex Edge System 18 User Manual ...
Page 29: ...Installation Drawings Vertex Edge System 28 User Manual ...
Page 46: ......
Page 59: ...Vertex Edge System 58 User Manual ...
Page 63: ...Vertex Edge System 62 User Manual ...
Page 69: ...Vertex Edge System 68 User Manual ...
Page 91: ...Vertex Edge System 90 User Manual ...
Page 96: ...Vertex Edge System 95 User Manual ...
Page 98: ...1 Main power ON OFF switch 2 Analyzer power switches Vertex Edge System 97 User Manual ...
Page 165: ... September 2021 1998 2002_EN_RevA1_VertexEdge_UserManual Vertex Edge System 164 User Manual ...