69
“C” Function
A
B
Defaults
Func.
Code
Name
Description
Initial
data
Units
EzCOM start adr. of master
1 to 8
1.
EzCOM end adr. of master
1 to 8
1.
EzCOM starting trigger
Input terminal
Always
00
Up/Down memory mode
selection
Controls speed setpoint for the inverter
after power cycle.
Two option codes:
Clear last frequency (return to default
frequency
)
Keep last frequency adjusted by
UP/DWN
00
Reset selection
Determines response to Reset input [RS].
Four option codes:
Cancel trip state at input signal ON
transition, stops inverter if in Run
Mode
Cancel trip state at signal OFF
transition, stops inverter if in Run
Mode
Cancel trip state at input ON
transition, no effect if in Run Mode
Clear the memories only related to
trip status
00
Restart mode after reset
Determines the restart mode after reset is
given, three option codes:
Start with 0 Hz
Start with freq. matching
Start with active freq. matching
00
-
UP/DWN clear mode
Freq. set value when UDC signal is given
to the input terminal, two option codes:
0 Hz
Original setting (in the EEPROM
memory at power on)
00
-
EO gain adjustment
Set range is 50. to 200.%
100.
%
AM gain adjustment
Set range is 50. to 200.%
100.
%
AM bias adjustment
Set range is 0. to 100.%
0.
%
Overload warning level 2
Sets the overload warning signal 2 level
between 0% and 200% (from 0 to two time
the rated current of the inverter)
Rated
current
x 1.15
A
Output [11] on delay
Set range is 0.0 to 100.0 sec.
0.0
s
Output [11] off delay
0.0
s
Output [12] on delay
0.0
s
Output [12] off delay
0.0
s
Relay output on delay
0.0
s
Relay output off delay
0.0
s
Logic output 1 operand A
All the programmable functions available
for logic (discrete) outputs except LOG1 to
LOG3, OPO, no
00
Logic output 1 operand B
00