38
Using Intelligent Output Terminals
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter outputs
a signal on that terminal when it is in Run
Mode. The output logic is active low, and is
the open collector type (switch to ground).
Option
Code
Terminal
Symbol
Function Name
State
Description
RUN
Run Signal
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Valid for inputs:
11, 12, AL0
– AL2
Example for terminal [11] (default output
configuration shown see
page 66
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration see
page 66
):
See I/O specs on
page 23, 24.
Required settings
(none)
Notes:
The inverter outputs the [RUN] signal whenever
the inverter output exceeds the start frequency
specified by parameter
.
The start frequency
is the initial inverter output frequency when it turns
ON.
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2
11
RUN
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
RUN
[FW,RV]
1
0
Output
frequency
t
Run
signal
start freq.
ON