54
“A” Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units
DC braking time for
deceleration
Sets the duration for DC
braking, range is from 0.0 to
60.0 seconds
0.5
s
DC braking / edge or
level detection for [DB]
input
Two options; select codes:
Edge detection
Level detection
01
DC braking force at
start
Level of DC braking force at
start, settable from 0 to 70 %
0.
%
DC braking time at start
Sets the duration for DC
braking, range is from 0.0 to
60.0 seconds
0.0
s
Carrier frequency
during DC braking
Carrier frequency of DC
braking performance, range is
from 2.0 to 10.0kHz
2.0
kHz
Frequency upper limit
Sets a limit on output
frequency less than the
maximum frequency
(
).
Range is from frequency
lower limit (
) to
maximum frequency
(
).
0.0 setting is disabled
>0.0 setting is enabled
0.00
Hz
Frequency upper limit,
2nd motor
0.00
Hz
Frequency lower limit
Sets a limit on output
frequency greater than zero.
Range is start frequency
(
) to frequency upper
limit (
)
0.0 setting is disabled
>0.0 setting is enabled
0.00
Hz
Frequency lower limit,
2nd motor
0.00
Hz
Jump freq. (center) 1 to
3
Up to 3 output frequencies
can be defined for the output
to jump past to avoid motor
resonances (center
frequency)
Range is 0.00 to 400.0 Hz
0.00
Hz
Jump freq. width
(hysteresis) 1 to 3
Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.00 to 10.0 Hz
0.50
Hz
Acceleration hold
frequency
Sets the frequency to hold
acceleration, range is 0.0 to
400.0
1
Hz
0.00
Hz
Acceleration hold time
Sets the duration of
acceleration hold, range is 0.0
to 60.0 seconds
0.0
s
PID enable
Enables PID function,
three option codes:
PID Disable
PID Enable
PID Enable with reverse
output
00
PID proportional gain
Proportional gain has a range
of 0.00 to 25.00
1.0