50
Main Profile Parameters
NOTE
:. Parameters marked with "
" in A column are accessible even in inverter running.
Parameters marked with "
" in B column are accessible even in inverter running when in
the high level access mode, which means that b031 is set to "10".
“F” Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units
Output frequency setting
Standard default target frequency
that determines constant motor
speed, range is 0.0 / start
frequency to maximum frequency
(A004)
0.00
Hz
Acceleration time (1)
Standard default acceleration,
range is 0.00 to 3600 sec.
10.00
s
Acceleration time (1),
2
nd
motor
10.00
s
Deceleration time (1)
Standard default deceleration,
range is 0.00 to 3600 sec.
10.00
s
Deceleration time (1),
2
nd
motor
10.00
s
Keypad RUN key routing
Two options; select codes:
Forward
Reverse
00