73
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
BOK
Brake confirmation
ON
Brake wait time (
) is valid
OFF Brake wait time (
) is not valid
LAC
LAD cancellation
ON
Set ramp times are ignored. Inverter output
immediately follows the freq. command.
OFF
Accel. and/or decel. is according to the
set ramp time
ADD
ADD frequency enable
ON
Adds the
(add frequency) value
to the output frequency
OFF
Does not add the
value to the
output frequency
F-TM
Force Terminal Mode
ON
Force inverter to use input terminals
for output frequency and Run command sources
OFF
Source of output frequency set by
and source
of Run command set by
is used
KHC
Clear watt-hour data
ON
Clear watt-hour data
OFF No action
MI1
General purpose input
(1)
ON
General purpose input (1) is made ON under EzSQ
OFF General purpose input (1) is made OFF under EzSQ
MI2
General purpose input
(2)
ON
General purpose input (2) is made ON under EzSQ
OFF General purpose input (2) is made OFF under EzSQ
MI3
General purpose input
(3)
ON
General purpose input (3) is made ON under EzSQ
OFF General purpose input (3) is made OFF under EzSQ
MI4
General purpose input
(4)
ON
General purpose input (4) is made ON under EzSQ
OFF General purpose input (4) is made OFF under EzSQ
MI5
General purpose input
(5)
ON
General purpose input (5) is made ON under EzSQ
OFF General purpose input (5) is made OFF under EzSQ
MI6
General purpose input
(6)
ON
General purpose input (6) is made ON under EzSQ
OFF General purpose input (6) is made OFF under EzSQ
MI7
General purpose input
(7)
ON
General purpose input (7) is made ON under EzSQ
OFF General purpose input (7) is made OFF under EzSQ
AHD
Analog command hold
ON
Analog command is held
OFF Analog command is not held
GS1
GS1 input
ON
EN60204-1 related signals:
Signal input of
“Safe torque off” function.
OFF
GS2
GS2 input
ON
OFF
485
Start EzCOM
ON
Starts EzCOM
OFF No execution
PRG
Executing EzSQ
program
ON
Executing EzSQ program
OFF No execution
HLD
Retain output frequency
ON
Retain the current output frequency
OFF No retention
ROK
Permission of Run
command
ON
Run command permitted
OFF Run command is not permitted
DISP
Display limitation
ON
Only a parameter configured in
is shown
OFF All the monitors can be shown
no
No function
ON
(input ignored)
OFF (input ignored)