33
Forward Run/Stop and Reverse Run/Stop Commands:
When you input the Run command via the terminal [FW], the inverter executes the Forward
Run command (high) or Stop command (low). When you input the Run command via the
terminal [RV], the inverter executes the Reverse Run command (high) or Stop command
(low).
Option
Code
Terminal
Symbol
Function Name
State
Description
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
Valid for inputs:
~
Example (default input configuration shown see
page 66
):
See I/O specs on
page 23, 24
.
Required settings
=
Notes:
When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
When a terminal associated with either [FW] or
[RV] function is configured for
normally closed
,
the motor starts rotation when that terminal is
disconnected or otherwise has no input voltage.
NOTE
: The parameter
, Keypad Run Key Routing, determines whether the single Run
key issues a Run FWD command or Run REV command. However, it has no effect on the
[FW] and [RV] input terminal operation.
WARNING:
If the power is turned ON and the Run command is already active, the motor
starts rotation and is dangerous! Before turning power ON, confirm that the Run command
is not active.
RV
FW
7
6
5
4
3
2
1
L
P24
PLC