“b” Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units
Reduced voltage
start selection
Set range,
(disabling the function),
(approx.
6ms) to
(approx. 1.5s)
2
Function code
display restriction
Six option codes:
Full display
Function-specific display
User setting (and
)
Data comparison display
Basic display
Monitor display only
00
Initial display
selection
Initial display selection by SET key.
to
to
displayed
displayed
B display of LCD operator
001
Automatic user
parameter
registration
Two option codes:
Disable
Enable
00
Controlled
deceleration on
power loss
Four option codes:
Trips
Decelerates to a stop
Decelerates to a stop with DC bus voltage
controlled
Decelerates to a stop with DC bus voltage
controlled, then restart
00
DC bus voltage
trigger level of ctrl.
decel.
Setting of DC bus voltage to start controlled
decel. operation. Range is 0.0 to 1000.0
220.0/
440.0
V
Over-voltage
threshold of ctrl.
decel.
Setting the OV-LAD stop level of controlled
decel. operation. Range is 0.0 to 1000.0
360.0/
720.0
V
Deceleration time
of ctrl. decel.
Range is 0.01 to 3600.0
1.0
s
Initial freq. drop of
ctrl. decel.
Setting of initial freq. drop.
Range is 0.00 to 10.0 Hz
0.0
Hz
Maximum-limit
level of window
comparator (O)
Set range, {Min.-limit level (
) + hysteresis
width (
)x2} to 100 %
(Minimum of 0%)
100.
%
Minimum-limit
level of window
comparator (O)
Set range, 0 to {Max.-limit level (
) -
hysteresis width (
)x2} % (Maximum of 0%)
0.
%
Hysteresis width
of window
comparator (O)
Set range, 0 to {Max.-limit level (
) -
Min.-limit level (
)}/2 % (Maximum of 10%)
0.
%
Maximum-limit
level of window
comparator (OI)
Set range, {Min.-limit level (
+ hysteresis
width (
)x2} to 100 %
(Minimum of 0%)
100.
%
Minimum-limit
level of window
comparator (OI)
Set range, 0 to {Max.-limit level (
) -
hysteresis width (
)x2} % (Maximum of 0%)
0.
%
Hysteresis width
of window
comparator (OI)
Set range, 0 to {Max.-limit level (
) -
Min.-limit level (
)}/2 % (Maximum of 10%)
0.
%
Operation level at
O disconnection
Set range, 0. to 100.%, or
“no” (ignore)
no
-
Operation level at
OI disconnection
Set range, 0. to 100.%, or
“no” (ignore)
no
-