24
Terminal Name
Description
Ratings
O
Analog voltage input
0 to 9.8 VDC range, 10 VDC nominal,
input impedance 10 k
H
+10V analog reference
10VDC nominal, 10mA max.
SP, SN
Serial communication terminal
For RS485 Modbus communication.
AL0, AL1, AL2 *3
Relay common contact
250VAC,
2.5A (R load) max.
250VAC,
0.2A (I load, P.F.=0.4) max.
100VAC, 10mA min.
30VDC,
3.0A (R load) max.
30VDC,
0.7A (I load, P.F.=0.4) max.
5VDC, 100mA min.
Note 1
:
The two terminals [L] are electrically connected together inside the inverter.
Note 2:
We recommend using [L] logic GND (to the right) for logic input circuits and [L]
analog GND (to the left) for analog I/O circuits.
Note 3:
Refer to page 41 for details of trip signals.
Note 4:
Refer to page 88,
“Functional Safety” for details
Wiring sample of control logic terminal (Source logic)
Note
:
If relay is connected to intelligent output, install a diode across the relay coil
(reverse-biased) in order to suppress the turn-off spike.
Caution for intelligent terminals setting
Please avoid conducting below procedure, because if you follow procedure describe below, the
inverter setting will be initialized.
1) Turning on power while [Intelligent input terminal 1/2/3 are ON] and [Intelligent input
terminal 4/5/6/7 are OFF].
2) After 1)
’s condition, turning off power.
3)
After 2)'s condition, turning on power while [Intelligent input terminal 2/3/4 are ON]
and [Intelligent input terminal 1/5/6/7 are OFF].