56
“A” Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units
Deceleration time (2)
Duration of 2
nd
segment of
deceleration, range is:
0.00 to 3600 sec.
10.00
s
Deceleration time (2),
2
nd
motor
10.00
s
Select method to switch
to Acc2/Dec2 profile
Three options for switching
from 1st to 2nd accel/decel:
2CH input from terminal
Transition frequency
Forward and reverse
00
Select method to switch
to Acc2/Dec2 profile, 2
nd
motor
00
Acc1 to Acc2 frequency
transition point
Output frequency at which
Accel1 switches to Accel2,
range is 0.00 to 400.0 Hz
0.0
Hz
Acc1 to Acc2 frequency
transition point,
2
nd
motor
0.0
Hz
Dec1 to Dec2 frequency
transition point
Output frequency at which
Decel1 switches to Decel2,
range is 0.00 to 400.0 Hz
0.0
Hz
Dec1 to Dec2 frequency
transition point,
2
nd
motor
0.0
Hz
Acceleration curve
selection
Set the characteristic curve of
Acc1 and Acc2, five options:
linear
S-curve
U-curve
Inverse U-curve
01
Deceleration curve
selection
Set the characteristic curve of
Dec1 and Dec2, options are
same as above (
)
01
[OI] input active range
start frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to 400.0 Hz
0.00
Hz
[OI] input active range
end frequency
The output frequency
corresponding to the current
input range ending point,
range is 0.00 to 400.0 Hz
0.00
Hz
[OI] input active range
start current
The starting point (offset) for
the current input range,
range is 0. to 100.%
20.
%
[OI] input active range
end current
The ending point (offset) for
the current input range,
range is 0. to 100.%
100.
%
[OI] input start
frequency select
Two options; select codes:
Use offset (
value)
Use 0Hz
00
Acceleration curve
constant
Range is 01 to 10.
2
Deceleration curve
constant
Range is 01 to 10.
2