60
“b” Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units
Overload
restriction
operation mode 2
Select the operation mode during overload
conditions, four options, option codes:
Disabled
Enabled for acceleration and constant
speed
Enabled for constant speed only
Enabled for acceleration and constant
speed, increase speed at regen.
01
Overload
restriction level 2
Sets the level of overload restriction, between
20 % and 150 % of the rated current of the
inverter, setting resolution is 1 % of rated
current
Rated
current
x 1.2
A
Deceleration rate
2 at overload
restriction
Sets the deceleration rate when inverter
detects overload, range is 0.1 to 3000.0,
resolution 0.1
1.0
s
OC suppression
selection
Two option codes:
Disabled
Enabled without voltage reduction
...Enable with voltage reduction
00
Current level of
active freq.
matching
Sets the current level of active freq. matching
restart, range is 0.1*inverter rated current to
2.0*inverter rated current, resolution 0.1
Rated
current
A
Deceleration rate
of active freq.
matching
Sets the deceleration rate when active freq.
matching restart, range is 0.1 to 3000.0,
resolution 0.1
0.5
s
Start freq. of
active freq.
matching
Three option codes:
freq at previous shutoff
start from max. Hz
start from set frequency
00
Software lock
mode selection
Prevents parameter changes, in five options,
option codes:
all parameters except
are locked
when [SFT] terminal is ON
all parameters except
and output
frequency
are locked when [SFT]
terminal is ON
all parameters except
are locked
all parameters except
and output
frequency
are locked
High level access including
See the row
“Run Mode Edit” for the accessible
parameters in this mode.
01
Motor cable length
parameter
Set range is 5. to 20.
10.
Run/power ON
warning time
Range is,
.
:Warning disabled
.
to
.
:
10 - 99,990 hrs (unit: 10)
to
:
100,000 - 655,350 hrs (unit: 100)
0.
Hrs.
Rotation direction
restriction
Three option codes:
No restriction
Reverse rotation is restricted
Forward rotation is restricted
00