63
“b” Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units
Cooling fan
control
(NOTE 1)
Selects when the fan is ON during inverter
operation, three options:
Fan is always ON
Fan is ON during run, OFF during stop (5
minute delay from ON to OFF)
Fan is temperature controlled
01
-
Clear elapsed
time of cooling fan
(NOTE 1)
Two option codes:
Count
Clear
00
-
Initialization target
data
Select initialized parameters, four option
codes:
All parameters
All parameters except in/output terminals
and communication.
Only registered parameters in
xxx.
All parameters except registered
parameters in
xxx and
.
00
-
Dynamic braking
control (BRD)
selection
Three option codes:
Disable
Enable during run only
Enable always
00
-
BRD activation
level
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
360/
720
V
BRD resistor
value
Set the value of the resistor connected to the
the inverter hardware is calculated
automatically.
Range is minimum connectable resistor Rbmin
to 600.0Ω
Min.
Resistance
Ω
Free V/F setting,
freq.1
Set range, 0 to value of
0.
Hz
Free V/F setting,
voltage.1
Set range, 0 to 800V
0.0
V
Free V/F setting,
freq.2
Set range, value of
to
0.
Hz
Free V/F setting,
voltage.2
Set range, 0 to 800V
0.0
V
Free V/F setting,
freq.3
Set range, value of
to
0.
Hz
Free V/F setting,
voltage.3
Set range, 0 to 800V
0.0
V
Free V/F setting,
freq.4
Set range, value of
to
0.
Hz
Free V/F setting,
voltage.4
Set range, 0 to 800V
0.0
V
Free V/F setting,
freq.5
Set range, value of
to
0.
Hz
Free V/F setting,
voltage.5
Set range, 0 to 800V
0.0
V
Free V/F setting,
freq.6
Set range, value of
to
0.
Hz