8 Troubleshooting
282
SMGB0064 rev.0 - 08/2011
Alarm code
EE
Compressor protection for IVX Series
• This alarm code is displayed when one of the following alarms occurs three times within six hours. If the outdoor unit
operates continuously without removing the cause of the alarm, the compressor may be seriously damaged
Alarm code
Content of abnormality
02
Tripping of protection device in outdoor unit
07
Decrease in discharge gas superheat
08
Increase in discharge gas temperature
41
Cooling overload
42
Heating overload
47
Low pressure decrease protection activating
You can check these alarms using the check mode 1. Follow the action that is indicated in each alarm chart. You can clear
these alarms only by turning OFF the main switch to the system.
However, you must pay careful attention before start-
ing, because there is a possibility of causing serious damages to the compressors.
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......