8 Troubleshooting
205
SMGB0064 rev.0 - 08/2011
8
Alarm codes for IVX and ES Series
Code
No.
Category
Type of Abnormality
Main cause
01
Indoor unit
Activation of protection device
Failure of fan motor, drain discharge, PCB, relay, float switch
activated.
02
Outdoor unit
Activation of protection device
Activation of PSH, locked motor, abnormal operation in the
power supply phase.
03
Transmission
Abnormality between indoor (or outdoor) and outdoor
(or indoor) units
Incorrect wiring. Failure of PCB. Tripping of fuse. Power
supply OFF.
04
Abnormal operation between inverter and control
PCB
Transmission failure between inverter PCBs
05
Power supply
Abnormal power supply
Power source with abnormal wave pattern.
06
Voltage drop
Voltage drop due to excessively low or high voltage in
outdoor unit
Voltage drop in power supply. Incorrect wiring or insufficient
capacity of power supply wiring.
07
Cycle
Drop in discharge gas overheating
Excessive refrigerant charge. Expansion valve lock open.
08
Increase in discharge gas temperature
Insufficient refrigerant charge, refrigerant leakage. Expansion
valve closed or clogged.
11
Sensor in indoor
unit
Inlet air thermistor
Failure of thermistor, sensor, connection.
12
Outlet air thermistor
13
Anti-freeze thermistor
14
Gas pipe thermistor
15
Fresh Outdoor Air Thermistor (Econofresh)
19
Protection device for fan motor is triggered
Failure of fan motor
20
Outdoor unit
sensor
Compressor thermistor
Failure of thermistor, sensor, connection.
22
Outside air thermistor
24
Evaporation thermistor
31
System
Incorrect setting of outdoor and indoor units
Incorrect setting of capacity code.
35
Incorrect setting of indoor unit number
Duplication of indoor unit number.
38
Abnormality of protective circuit in outdoor unit
Failure of indoor unit PCB; incorrect wiring; connection to
indoor unit PCB.
41
Pressure
Cooling overload (possible activation of high pressure
device)
O.U. pipe thermistor temp. is higher than 55 ºC and the
compressor top temp. is higher than 95 ºC, O.U. protection
device is activated.
42
Heating overload (high-pressure device may be
activated)
If I.U. freeze protection thermistor temp. is higher than 55 ºC
and compressor top temp. is higher than 95 ºC, O.U. protec-
tion device is activated.
47
Activation of protection device for low pressure drop
Stoppage due to excessive decrease of evaporating temper-
ature (Temp < -35 ºC) is activated 3 times in one hour, motor
locked in heating mode.
48
Inverter
Activation of overcurrent protection
Overload, overcurrent. Failure of DIP IPM, IPM or PCB2,
heat exchanger clogged, locked compressor.
51
Abnormality in inverter current sensor
Incorrect wiring of current sensor. Failure of control PCB, DIP
IPM, IPM or PCB2.
52
Abnormal thermistor of inverter fin (for inverter fin
temperature)
Shorcircuit or incorrect wiring
53
Activation for protection of DIP IPM, IPM or PCB2
Abnormality of DIP IPM or PCB2
Compressor failure, heat exchanger clogged.
54
Increase in inverter fin temperature
Abnormal inverter fin thermistor
Heat exchanger clogged.
Abnormal outdoor fan.
55
Abnormality of DIP IPM, IPM or PCB2
Failure of DIP-IPM, IPM or PCB2.
57
Outdoor fan
Fan motor abnormality
Disconnected wire or incorrect wiring between control PCB
and inverter PCB.
Incorrect wiring or abnormality in fan motor.
59
Inverter
Abnormal inverter fin thermistor (for the temperature
of inverter fin)
Lost terminals, disconnected wire, failure of inverter thermis-
tor.
EE
Compressor
Compressor protection alarm
Compressor failure.
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......