8 Troubleshooting
290
SMGB0064 rev.0 - 08/2011
8.2.3 Troubleshooting by means of the 7-segment display
Simple checking by 7-segment display
• During auto-addressing, the following items can be checked using the outdoor unit’s on-board 7-segment LED display:
1.
Disconnection of power supply to the indoor unit.
2.
Reverse connection of the operating line between the outdoor and indoor units.
3.
Duplication of indoor unit number.
• Outdoor Unit, Circuit Board, PCB1
1.
Turn ON all Indoor Units connected to the Outdoor Unit
2.
Turn ON the Outdoor Unit
3.
Auto-addressing starts
Checking method by 7-segment display
Operating conditions and each part of refrigeration cycle can be checked by 7-segment and push switches (PSW) on the
PCB in the outdoor unit. During checking data, do not touch the electric parts except for the indicated switches because
220-240 V (400 V in case of RAS-(4-6)HRN(M/S)2E, RAS-(8-12)HRNM and RAS-(8/10)HRNSE) is applied to them. Pay
attention not to contact the tools with electrical parts. If contacted, electrical parts will be damaged.
• To start checking, press PSW2 switch for more than three sec-
onds.
• To proceed checking, press the PSW2 switch.
• To back to the previous item, press the PSW3 switch.
• To cancel this checking, press the PSW2 switch for more than
3 seconds
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......