12 Maintenace notes
470
SMGB0064 rev.0 - 08/2011
12.9 Service and maintenance record
No.
Check item
Action
Judgement
1
Is the service area sufficient?
—
Yes
No
2
Is there a short circuit of the discharged air?
—
Yes
No
3
Any heat influence?
—
Yes
No
4
Is the ground wire connected?
—
Yes
No
5
Refrigerant piping.
—
Good
Not Good
6
Fixing the units.
—
Good
Not Good
7
Is there any damage on the outer surface or
the internal surface?
—
Yes
No
8
Checking the screw and the bolts.
Tighten if loosened.
Tightened
Not Tightened
9
Tightening the terminal screws.
Tighten all the terminal screws with a Phillips
screwdriver.
Tightened
Not Tightened
10
Are the compressor terminals tightly fixed?
Push all the terminals.
Pushed
Not Pushed
11
Insulation resistance.
Measure the insulation resistance with an insula-
tion resistance meter.
Comp. and fan.
motor: greater than 3MΩ.
Others: greater than 3MΩ.
Good
Not Good
12
Does the drain water flow smoothly?
Check the smooth flow by pouring some water.
Good
Not Good
13
Check for a leakage in the compressor.
Check for any leakage.
Good
Not Good
14
Check for a leakage in the outdoor heat ex-
changer.
ditto
Good
Not Good
15
Check for a leakage in the indoor heat exchan-
ger.
ditto
Good
Not Good
16
Check for a leakage in the 4-way valve.
ditto
Good
Not Good
17
Check for a leakage in the check valve.
ditto
Good
No Good
18
Check for a leakage in the accumulator.
ditto
Good
Not Good
19
Check for a leakage in the strainer.
ditto
Good
Not Good
20
Check for a leakage in the electronic expansion
valve
ditto
Good
Not Good
21
Check for a leakage in the piping.
ditto
Good
Not Good
22
Check the direction of the fans.
By viewing the airflow volume.
Good
Not Good
23
Voltage among each phase.
Higher than AC220V.
Good
Not Good
24
Vibration and sound.
Check the fan the compressor the piping and
others.
Good
Not Good
25
Activation of each operation mode.
Check the activation of the COOL switch the
HEAT switch the STOP switch and the TEMP
switch.
Good
Not Good
26
High-pressure cut-out switch.
Check the actual activation value.
Good
Not Good
27
Check the activation of the drain-up mecha-
nism.
Check the activation during the cooling process.
Good
Not Good
28
Air inlet temperature of the indoor unit DB/WB.
—
(°C)DB
(°C)WB
29
Air outlet temperature of the indoor unit DB/
WB.
—
(°C)DB
(°C)WB
30
Air inlet temperature of the outdoor unit DB/
WB.
—
(°C)DB
(°C)WB
31
Air outlet temperature of the outdoor unit DB/
WB.
—
(°C)DB
(°C)WB
32
High-pressure switch.
—
kg/cm
2
G
33
Low-pressure switch.
—
kg/cm
2
G
34
Operating voltage.
—
V
35
Operating current.
—
A
36
Instructions to the client for cleaning the air
filter.
—
Done
Not yet
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......