7 Test Run
180
SMGB0064 rev.0 - 08/2011
7.4 Test run procedure from the outdoor unit side
The test run procedure from the outdoor unit side is shown below.
You can set this DIP switch while the power source is ON.
Setting of dip switch
DSW1
1
Cooling: Pin 1 ON
2
Heating: Pin 1, 2 ON
3
Cooling intermediate season: Pin 1, 3 ON
4
Heating intermediate season: Pin 1, 2, 3 ON
5
Manual compressor OFF: Pin 4 ONe
D A N G E R
•
Do not touch any other electrical components while you are setting the switches on the PCB.
•
Do not attach or detach the service access panel when the power source for the outdoor unit is ON and the
outdoor unit is operating.
•
Set all the DIP switches of DSW1 to OFF after completing the test run.
Dip switch seting
Operation
Remarks
Test run
1. Setting operation mode
•
The indoor unit automatically
starts to operate when the
test run of the outdoor unit
is set.
•
You can perform the ON/OFF
operation from the remote
control switch or the DSW1
of the outdoor unit.
•
Continuous operation during
2 hours is performed without
the Thermo-OFF condition.
•
Make sure that the indoor
units start to operate in
accord with the test run of
the outdoor unit.
•
If you start the test run from
the outdoor unit and you stop
the test run from the remote
control switch, the test run
function of the remote control
switch is cancelled. Howe-
ver, the test run function
of the outdoor unit is not
cancelled.
•
If the more than one indoor
unit is connected with one
remote control switch, all the
units start the test run at the
same time. Therefore, turn
OFF the power source so
that the indoor units do not
perform the test run. If this is
the case, the TEST RUN in-
dication of the remote control
switch may flicker. This is not
abnormal.
•
The setting of DSW1 is not
required for the test run from
the remote control switch.
(a) Cooling:
Set DSW1-1 ON
(b) Heating
SET DSW1-1 and 2 ON
(c) Cooling intermediate
season:
Set DSW1-1 and 3 ON
(d) Heating intermediate
season:
Set DSW1-1, 2 and 3 ON
Manual OFF of com-
pressor
2. Forced stoppage of compressor:
•
When DSW1-4 is ON during
the compressor operation,
the compressor stops
operating immediately and
the indoor unit is under the
Thermo-OFF condition.
•
When DSW1-4 is OFF, the
compressor starts to operate
after the cancellation of the
3-minute guard.
•
Do not turn ON and OFF the
compressor frequently
Set DSW1-1 ON
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......