8 Troubleshooting
321
SMGB0064 rev.0 - 08/2011
8
•
Checking procedure for the electronic expansion valve
Valve position
Electronic expansion valve
Outdoor unit electronic expansion valve
Locked fully closed
Check the temperature of the piping in the heat-
ing process. Failure of the temperature to rise
indicates a fault.
It is abnormal if the liquid pipe pressure does
not increase during the cooling process.
Locked slightly open
The following conditions indicate a fault:
-
Where the freeze protection thermistor tempe-
rature is lower than the intake air temperature.
-
Where the unit being inspected stops and
other units continue operating in cooling mode.
Electronic expansion valve
Freeze protection thermistor
It is abnormal if the liquid pipe pressure does
not increase and the outlet temperature of the
expansion valve decreases after the cooling
process starts.
Locked fully open
It is abnormal under the following conditions:
after the heating process for more than 30
minutes, the discharge gas temperature of
the compressor is not 10°C higher than the
condensing temperature and there is no other
faults, such as an excessive charge of refriger-
ant and others.}
•
Fault diagnosis of DC fan motor
About fan motor fault diagnosis.
When ISPM/DIP-IPM is faulty and Alarm 53 appears, the fan motor may also be damaged. To prevent ISPM/DIP-IPM
damage which may result from operation combined with a faulty fan motor, check also if the fan motor is not damaged
when ISPM/DIP-IPM is replaced.
C A U T I O N
-
For the shake of safety, turn OFF the power before start working.
-
Working/checking with the power ON may disturb correct diagnosis and may result in failure.
Models for ES:
DC motor(s) included in different models:
Model
Pieces
RAS-(2/2.5)HVRN2
1
RAS-3HVRNS2
1
RAS-(4-6)H(V)RNS2E
1
RAS-(8/10)HRNSE
1
Fault diagnosis procedure
1.
Remove fan motor connectors from the control PCB ISPM or DIP-IPM and turn the fan motor shaft by hand.
Normal:
Fan motor shaft turns smoothly.
Faulty:
No continuous rotary torque movement felt when turning the motor by hand. This occurs because the internal
magnet of the fan motor breaks the movement when the internal electronic circuit of the fan motor has a short-
circuit fault
2.
Measure the fan motor resistance using a tester.
Measurement procedure:
1.
Remove the fan motor connector from the control PCB, ISPM or DIP-IPM.
2.
Connect the black test lead of the tester to the black wire pin of the fan motor connector
3.
Connect the red test lead to the wire connector pin to be checked
Results
Normal:
Observed values will be close to the normal values in the table below
Faulty:
Observed values will be deviated from the normal values in the table below.
Generally an open-circuit fault shows ∞, and a short-circuit fault shows several Ω-kΩ.)
Internal electronic circuit fault of the fan motor including short-circuit and breakage can be checked
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......