8 Troubleshooting
198
SMGB0064 rev.0 - 08/2011
8.1.3 Abnormal transmission between the remote control switch and the indoor unit
•
RUN LED on the remote control switch:
Flickering every 2 seconds.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Disconnection or insufficient contacting of the remote control cable
Check the cable and the connec-
tions
Repair the cable or connect the
cable
Failure of the remote control switch
Check the remote control switch
by means of the self-check mode
*1)
Replace the remote control switch
if the remote control switch is
faulty
Failure of PCB (in the indoor unit
and the remote control switch)
Disconnected wire to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the self-
check mode *2)
Replace PCB if it failed
N O T E
•
*1): Refer to section
Self-checking of the remote control switch
, see on page 301
.
•
*2): Refer to section
Self-checking procedure of PCB by means of the Remote Control Switch
, see on page 299
.
8.1.4 Abnormal operation of the devices
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
RUN LED is ON and
the LCD is indicated.
However, the system
does not operate (For
example, the indoor
fan, the outdoor fan or
the compressor does
not operate)
Failure of the indoor unit
fan motor
Disconnected coil
Measure the coil resistance by
means of the tester
Replace the Indoor unit fan
motor
Burnt-out coil
Measure the insulation resist-
ance
Failure of the outdoor
unit fan motor
Disconnected coil
Measure the coil resistance by
means of the tester
Replace the outdoor unit fan
motor
Burnt-out coil
Measure the insulation resist-
ance
Failure of the magnetic
switch for the outdoor
unit fan motor
Insufficient contacting
Measure the voltage between
the contacting parts
Replace PCB for the outdoor
unit
Failure of the comp. motor
Measure the resistance be-
tween two wires
Replace the compressor
Failure of the comp.
Check for an abnormal sound
from the Comp.
Failure of the magnetic
switch for comp.
Insufficient contacting
Check that the magnetic switch
activates correctly or not
Replace the magnetic switch
Failure of one of PCBs
Disconnected wiring
to PCB
Check the connections
Correctly connect the wiring
Failure of PCB
Check PCB by means of the
self-check mode *1)
Replace PCB if it failed
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......