8 Troubleshooting
248
SMGB0064 rev.0 - 08/2011
Alarm code
35
Incorrect Indoor number setting
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, alarm code and unit model code appear alternately on the Set Temperature display of the remote
control switch. The alarm code also appears on the outdoor unit PCB display.
-
The alarm code appears three minutes after the outdoor unit power activation if duplication is detected in indoor
unit numbers connected to an outdoor unit (one refrigerant system). This applies when indoor unit numbers are
configured using the rotary switch (RSW1).
-
The alarm code appears when five or more indoor units are connected to one outdoor unit.
-
The alarm code appears when the indoor and outdoor unit refrigerant system and address are set to 64 or above.
(In such a case, the alarm code “b1” appears on the remote control switch.)
N O T E
The alarm code may appear when H-LINK system is employed for indoor–outdoor unit transmission, if there is
any incorrect setting in DSW4/RSW1 on the outdoor unit PCB and DSW5/RSW2 on the indoor unit PCB; which
are dip switches used for refrigerant system setting. In such a case, turn OFF the power and correctly set DSW4/
RSW1 on the outdoor unit PCB and DSW5/RSW2 on the indoor unit PCB before reactivating the power.
(Some indoor unit models do not have RSW2.)
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......