3 Piping work and
refrigerant charge
59
SMGB0064 rev.0 - 08/2011
3
3.2.8 Pump down refrigerant
When the refrigerant should be collected into the outdoor unit due to indoor/outdoor unit relocation, collect the refrigerant
as follows:
1
Attach the manifold gauge to the gas stop valve and the liquid stop valve.
2
Turn ON the power source.
3
Set the DSW1-1 pin of the outdoor unit PCB at the “ON” side for cooling operation. Close the liquid stop valve and col-
lect the refrigerant.
4
When the pressure at lower pressure side (gas stop valve) indicates -0.01 MPa (-100 mmHg), perform the following
procedures immediately.
• Close the gas stop valve.
• Set the DSW1-1 pin at the “OFF” side (To stop the unit operation).
5
Turn OFF the power source.
C A U T I O N
Measure the low pressure by the pressure gauge and keep it in a measurement higher than -0.01 MPa. If the pres-
sure is lower than -0.01 MPa, the compressor may be faulty.
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......