8 Troubleshooting
297
SMGB0064 rev.0 - 08/2011
8
The activating conditions of protection control are shown in the table below
Code
Protection Control
Activating Condition
Remarks
P0
Low-Pressure Ratio Control at Cooling
Operation
Compression Ratio ε < 2.2
=> Frequency Increase
ε = (Pd+0.1)/(Ps+0.1)
P1
High-Pressure Ratio Control at Heating
Operation
Compression Ratio ε > 7.5
=> Frequency Decrease
ε = (Pd+0.1)/(Ps+0.1)
P2
High-Pressure Increase Protection
High Pressure Switch for Control is activated
=> Frequency Decrease
—
P3
Over Current Protection
Inverter Output Current > (*1)A
=> Frequency Decrease
—
P4
DIP-IPM, ISPM or IPM Temperature
Increase Protection
Inverter Fin Temperature
RAS-8~10HRNSE > 100 ºC
RAS-3~6HVRNS2(E) > 80 ºC
=> Frequency Decrease
—
P5
Discharge Gas Temperature Increase
Protection
Temperature at the top of compressor is high
=> Frequency Decrease
Temperature at the top of compressor > 107 ºC
=> Indicate P5
—
P6
Frost Formation Protection
TL ≤ 2 °C Over 3 minutes => Frequency Decrease
TL: Liquid Piping,
Temperature of Indoor Unit
P9
Unbalance Power Source Detecting
Inverter Output Current > (*3)A
=> Frequency Decrease
—
PA
Current Demand Control
Inverter Output Current > (*2)A
=> Frequency Decrease
In case of
Demand Control Setting
Pb
Low-Pressure Decrease Protection
Low Pressure Switch for Control is activated.
=> Frequency Decrease
—
PC
Cold Draft Protection
TO ≤ 10 ºC and ε ≥ 2.6 => Frequency Decrease
ε = (Pd+0.1)/(Ps+0.1)
TO: Outlet Temperature of
Indoor Unit
P7
Inverter Retry
Automatic Stoppage of Transistor Module,
Activation of Electronic Thermal or Abnormal Current
Sensor
When activating 3 times in 30
minutes, “48”, “51”, “53” or “54”
alarm is indicated.
P8
Inverter Retry
Insufficient/Excessive Voltage at Inverter
Circuit or PCB Connector Part
When activating 3 times in 30
minutes, “06” or “55” alarm is
indicated.
N O T E
•
During protection control (except during alarm stoppage), the protection control code is indicated.
•
The protection control code is indicated during protection control and turns off when cancelling the protection
control.
•
After retry control, the condition of monitoring is continued for 30 minutes.
•
The Maximum value of IVX series (*1) and (*2) are as follows:
•
The Maximum value of ES series (*3), (*4) and (*5) are as follows:
(1*)
HP
380-415V
220-240V
4
5
6
8
10
12
3
4
5
6
Current (A)
8.0
12.0
12.0
17.5
20.0
21.0
16.0
16.0
24.0
24.0
(2*)
HP
380-415V
220-240V
Demand setting
4
5
6
8
10
12
3
4
5
6
Current (A)
100%
4.0
5.5
20.0
8.5
10.0
12.0
11.5
13.0
17.0
20.0
75%
3.0
4.0
15.0
6.0
8.0
12.0
8.5
10.0
13.0
15.0
50%
2.0
2.0
10.0
4.0
5.0
7.5
5.5
6.5
8.5
10.0
Summary of Contents for RAS-(2-3)HVRN(S)(2)
Page 2: ......
Page 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Page 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Page 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Page 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Page 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Page 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Page 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Page 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Page 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Page 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Page 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Page 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Page 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Page 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Page 170: ......
Page 182: ......
Page 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Page 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Page 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Page 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Page 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Page 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Page 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Page 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Page 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Page 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Page 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Page 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Page 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Page 368: ......
Page 448: ......
Page 470: ......
Page 487: ......