4-15
Chapter 4
For parameter configuration
[Ab-01]
~
[Ab-25]
Scaled Output
Frequency gain monitor [dA-06]
Code/Name
Range (unit)
Initial value
Ab-01
Frequency
conversion gain
0.00
~
100.00
1.00
・
The visualized “Scaled Output frequency [dA-06]” is
equal to the “Output frequency [dA-01]” multiplied by the
“Frequency scaling conversion factor[Ab-01]”.
Multispeed command
Code/Name
Range (unit)
Initial
value
Ab-03
Multispeed operation
selection
00(16 speeds)/
01(8 speeds)
00
Ab110
Multispeed-0, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-11
Multispeed-1, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-12
Multispeed-2, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-13
Multispeed-3, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-14
Multispeed-4, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-15
Multispeed-5, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-16
Multispeed-6, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-17
Multispeed-7, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-18
Multispeed-8, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-19
Multispeed-9, 1st-motor
0.00
~
590.00(Hz)
0.00
Ab-20
Multispeed-10, 1st-motor 0.00
~
590.00(Hz)
0.00
Ab-21
Multispeed-11, 1st-motor 0.00
~
590.00(Hz)
0.00
Ab-22
Multispeed-12, 1st-motor 0.00
~
590.00(Hz)
0.00
Ab-23
Multispeed-13, 1st-motor 0.00
~
590.00(Hz)
0.00
Ab-24
Multispeed-14, 1st-motor 0.00
~
590.00(Hz)
0.00
Ab-25
Multispeed-15, 1st-motor 0.00
~
590.00(Hz)
0.00
・
For the 16 speeds selection, set [Ab-03]=03 for
assigning the intelligent terminals 003[CF1] to
006[CF4] makes available the use of the speeds 0 to
15.
Multispeed
CF4
CF3
CF2
CF1
Speed 0
OFF
OFF
OFF
OFF
Speed 1
OFF
OFF
OFF
ON
Speed 2
OFF
OFF
ON
OFF
Speed 3
OFF
OFF
ON
ON
Speed 4
OFF
ON
OFF
OFF
Speed 5
OFF
ON
OFF
ON
Speed 6
OFF
ON
ON
OFF
Speed 7
OFF
ON
ON
ON
Speed 8
ON
OFF
OFF
OFF
Speed 9
ON
OFF
OFF
ON
Speed 10
ON
OFF
ON
OFF
Speed 11
ON
OFF
ON
ON
Speed 12
ON
ON
OFF
OFF
Speed 13
ON
ON
OFF
ON
Speed 14
ON
ON
ON
OFF
Speed 15
ON
ON
ON
ON
[Ab210][AC-01]
~
[AC-02]
・
For the 8 speeds selection, set [Ab-03]=01 assigning the
intelligent terminals 007[SF1] to 013[SF7] makes
available the use of the speeds 0 to 7.
Multispeed
SF7
SF6
SF5
SF4
SF3
SF2
SF1
Speed 0
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Speed 1
-
-
-
-
-
-
ON
Speed 2
-
-
-
-
-
ON
OFF
Speed 3
-
-
-
-
ON
OFF
OFF
Speed 4
-
-
-
ON
OFF
OFF
OFF
Speed 5
-
-
ON
OFF
OFF
OFF
OFF
Speed 6
-
ON
OFF
OFF
OFF
OFF
OFF
Speed 7
ON
OFF
OFF
OFF
OFF
OFF
OFF
2nd motor
When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range (unit)
Initial
value
Ab210
Multispeed-0, 2nd-motor
Same as Ab110
Input method for Acc/Decel time
Code/Name
Range (unit)
Initial
value
AC-01
Acceleration/Deceleration
Time input selection
00(Parameter)/
01(Option 1)/
02(Option 2)/
03(Option 3)/
04(Function EzSQ)
00
・
[AC-01] changes the reference target for the Acc/Decel
command.
Individual Acc/Decel for Multispeed
Code/Name
Range (unit)
Initial value
AC-02
Acceleration/
Deceleration selection
00(Common)/01(Multi)
00
・
When [AC-02]=00, the acceleration/deceleration time
settings [AC120][AC122] or [AC124][AC126] will be in
effect.
・
2-stage acceleration/deceleration functions from
[AC115] to [AC117] can be set.
・
When [AC-02]=01, the acceleration/deceleration time
[AC-30]
~
[AC-88] for each multispeed control (from
speed 1 to 15) are enabled.
・
When [AC-02]=01, while in Multspeed-0 command,
Acc/Decel setting [AC120] [AC122] or Acc/Decel setting
[AC124] [AC126] are enabled.
・
During remote control up/down [FUP]/[FDN]
(parameters [CA-64] and [CA-66]) and PID soft start
(parameter [AH-78]), those parameters can be
overwritten.