4-21
Chapter 4
For parameter configuration
[AG101]
~
[AG113]
Resonant frequency avoidance (Jump)
Code/Name
Range (unit)
Initial
value
AG101
Jump frequency 1, 1st-motor
0.00
~
590.00(Hz)
0.00
AG102
Jump frequency width
1,
1st-motor
0.00
~
10.00(Hz)
0.00
AG103
Jump frequency 2, 1st-motor
0.00
~
590.00(Hz)
0.00
AG104
Jump frequency width 2,
1st-motor
0.00
~
10.00(Hz)
0.00
AG105
Jump frequency 3, 1st-motor
0.00
~
590.00(Hz)
0.00
AG106
Jump frequency width 3,
1st-motor
0.00
~
10.00(Hz)
0.00
・
Prevents the passing of the output frequency in a
resonant point. Output frequency changes continuously.
Motor Acc/Decel dwell (Hold)
Code/Name
Range (unit)
Initial
value
AG110
Acceleration stop frequency
setting, 1st-motor
0.00
~
590.00(Hz) 0.00
AG111
Acceleration stop time setting,
1st-motor
0.00
~
60.00(s)
0.00
AG112
Deceleration stop frequency
setting, 1st-motor
0.00
~
590.00(Hz) 0.00
AG113
Deceleration stop time setting,
1st-motor
0.00
~
60.00(s)
0.00
・
By using the dwell function when the inertial load is
considerable, if the set frequency is reached in the set
time the Acc/Decel of the frequency will be stopped.
・
If the Intelligent input terminal function 100[HLD] is in
ON state, the acceleration and deceleration will be
stopped (Hold activation).
[AG-20]
~
[AG213]
Jogging function
Code/Name
Range (unit)
Initial
value
AG-20
Jogging
frequency
0.00
~
10.00(Hz)
0.00
AG-21
Jogging stop
selection
00(free-running, disabled during operation)
01(decel/stop, disabled during operation)
02(DC braking, disabled during operation)
03(free-running, enabled during operation)
04(decel/stop, enabled during operation)
05(DC braking, enabled during operation)
00
・
When Input terminal [JG] is active (ON), if the operation
command is given the jogging frequency is outputted.
The frequency and stop method can be set when
performing jogging motion.
2nd motor
When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range
(unit)
Initial
value
AG201
Jump frequency 1, 2nd-motor
Same as AG101
AG202
Jump frequency width 1, 2nd-motor
Same as AG102
AG203
Jump frequency 2, 2nd-motor
Same as AG103
AG204
Jump frequency width 2, 2nd-motor
Same as AG104
AG205
Jump frequency 3, 2nd-motor
Same as AG105
AG206
Jump frequency width 3, 2nd-motor
Same as AG106
AG210
Acceleration stop frequency setting,
2nd-motor
Same as AG110
AG211
Acceleration stop time setting 2nd-motor
Same as AG111
AG212
Deceleration stop frequency setting,
2nd-motor
Same as AG112
AG213
Deceleration stop time setting,,
2nd-motor
Same as AG113
Output
frequency
Frequency
reference
[AG101]
[AG103]
[AG105]
[AG102]
[AG102]
[AG104]
[AG104]
[AG106]
[AG106]
[AG111]
[AG110]
Output
Frequency
Time
[AG112]
[AG113]
JG
FW
RV
Output
Frequency
[AG-20]
Summary of Contents for P1-00041HFEF
Page 6: ...0 5 Contents Contents Memo ...
Page 42: ...2 26 Chapter 2 Installation and Wiring Memo ...
Page 129: ...Index Index 3 memo ...
Page 130: ...Index Index 4 memo ...