4-45
Chapter 4
For parameter configuration
[CF-01]
~
[CF-10]
Modbus communication
Code/Name
Range (unit)
Initial
value
CF-01
RS485 communication baud
rate selection
03(2400bps)/
04(4800bps)/
05(9600bps)/
06(19.2kbps)/
07(38.4kbps)/
08(57.6kbps)/
09(76.8kbps)/
10(115.2kbps)
05
CF-02
RS485 communication
Node allocation
1
~
247
1
CF-03
RS485 communication
parity selection
00(Absent)/
01(Even parity)/
02(Odd parity)
00
CF-04
RS485
communication stop-bit
selection
01(1bit)/02(2bit)
01
CF-05
RS485 communication
erroort selection
00(Error)/
01(Tripping
after
deceleration
and
stopping
the
motor)/
02(Ignore errors)/
03(Stopping
the
motor
after
free-run)/
04(Deceleration and
stopping the motor)
02
CF-06
RS485 communication trip limit
time setting (timeout)
0.00
~
100.00(s)
0.00
CF-07
RS485 communication
wait time
0
~
1000(ms)
0
CF-08
RS485 communication
mode selection
01(Modbus-RTU)/
02(EzCOM)/
03(EzCOM control)
01
・
Sets the Modbus communication function for its use.
・
When using communication function between inverter
EzCOM, set a value except 01 for [CF-08].
[CF-20]
~
[CF-50]
EzCOM peer to peer communication
Code/Name
Range (unit)
Initial
value
CF-20
EzCOM Start node No.
01
~
08
01
CF-21
EzCOM End node No.
01
~
08
01
CF-22
EzCOM Start selection
00(Terminal
ECOM)/
01(Always)
00
CF-23
EzCOM data size
01
~
05
05
CF-24
EzCOM destination address 1
1
~
247
1
CF-25
EzCOM destination register 1
0000
~
FFFF
0000
CF-26
EzCOM source register 1
0000
~
FFFF
0000
CF-27
EzCOM destination address 2
1
~
247
2
CF-28
EzCOM destination register 2
0000
~
FFFF
0000
CF-29
EzCOM source register 2
0000
~
FFFF
0000
CF-30
EzCOM destination address 3
1
~
247
3
CF-31
EzCOM destination register 3
0000
~
FFFF
0000
CF-32
EzCOM source register 3
0000
~
FFFF
0000
CF-33
EzCOM destination address 4
1
~
247
4
CF-34
EzCOM destination register 4
0000
~
FFFF
0000
CF-35
EzCOM source register 4
0000
~
FFFF
0000
CF-36
EzCOM destination address 5
1
~
247
5
CF-37
EzCOM destination register 5
0000
~
FFFF
0000
CF-38
EzCOM source register 5
0000
~
FFFF
0000
・
Set for the use of EzCOM function.
・
For more information, refer to the User’s guide.
USB node code
Code/Name
Range (unit)
Initial
value
CF-50
USB communication
node selection
1
~
247
1
・
Sets the USB code in the case of multiple inverter
connections with ProDriveNext(PC software), as is also
required in the ProDriveNext side.