Chapter IV Function Parameter Table
95
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
terminal, and the value of each bit
represents the status of the
corresponding terminal. For specific bit
definition, please refer to the
communication address 0x1207
description.
Fd.12
VDO3
terminal
function
selection
1
0
×
Fd.13
VDO4
terminal
function
selection
1
0
×
Fd.14
VDO5
terminal
function
selection
1
0
×
Fd.15
VDO1
output on
delay
Same as F6.29
~
F6.34 function code
setting.
0.1s
0.0s
○
Fd.16
VDO2
output on
delay
0.1s
0.0s
○
Fd.17
VDO3
output on
delay
0.1s
0.0s
○
Fd.18
VDO4
output on
delay
0.1s
0.0s
○
Fd.19
VDO5
output on
delay
0.1s
0.0s
○
FE group: Water pump protection function 1
FE.00
Dry run
detection
current
FE.00 setting range: 0.0
~
100.0% motor
rated current
FE.01 setting range: 0.0
~
300.0s dry run
detection time
When FE.00 = 0.0, dry run detection is
not performed
When the drive’s running current is less
than the dry run detection current, and the
running frequency reaches the upper limit
frequency. Drive waits for the dry run
detection time and displays E032 dry run
alarm if the above condition persists.
0.1%
50.0%
×
FE.01
Dry run
detection
time
0.1s
0.0
×
FE.02
Motor stall
protection
time
FE.02 setting range: 0.0
~
6000.0s
FE.03 setting range: lower limit frequency
~ upper limit frequency
FE.03 setting range: 0.0
~
100.0% drive’s
rated current
When the motor stall protection time is 0,
the motor stall detection is disabled.
When the operating frequency is less than
the motor stall detection frequency and
0.1s
0.0s
×
FE.03
Motor stall
detection
frequency
0.01Hz
10.00hz
×
FE.04
Motor stall
current
0.1%
50.0%
×