Chapter V Basic Operation Instructions
116
Set value
Function
Description
ON
ON
ON
ON
Multistage
instruction
16
16
Acceleration/deceleration time
selection 1
The ON/OFF combination of acceleration/deceleration
time terminals 1 and 2 can realize the selection of
acceleration/deceleration time 1~4.
K2
K1
Acceleration/deceler
ation time selection
OFF
OFF
Acceleration/deceler
ation time 1
OFF
ON
Acceleration/deceler
ation time 1
ON
OFF
Acceleration/deceler
ation time 3
ON
ON
Acceleration/deceler
ation time 4
17
Acceleration/deceleration time
selection 2
18
PLC pause
Used to realize the pause control of the PLC running
process. When this terminal is valid, it runs at zero
frequency. The PLC running is not counted.
19
PLC operation stop and reset
PLC is prohibited from starting when the terminal is
valid, deceleration and stop control is implemented for
the PLC running process, and the PLC is reset to the
initial state.
20
PID control pause
PID is temporarily invalid, and the drive maintains the
current output frequency without performing PID
adjustment.
21
PID parameter switching
When the PID parameter switching condition (F8.12) is
set to 1 (via terminal switching), the F8.06~F8.08 are
used for PID parameters when the terminal is invalid,
and F8.09~F8.11 are used when the terminal is valid.
22
Counter trigger
Count pulse input port of the built-in counter, the highest
pulse frequency: 200Hz, and the current count value can
be stored and memorized when power is off. See
function codes F6.22 and F6.23 for details.
23
Counter reset
Clear the built-in counter of the drive and use it in
conjunction with function 22 (counter trigger signal
input).
24
Length reset
When the function terminal is valid, the actual length is
cleared to zero.
25
Acceleration/deceleration
prohibited (level)
Keep the motor from being affected by any external
signal (except stop command), maintain operating at the
current speed. This function is invalid during jog
running.
26
Immediate DC braking
When the stop mode is “decelerate and stop + DC
brake”, it is switched to DC brake status when the
terminal is valid during stop.
27
UP/DOWN setting cleared
When the frequency input channel is set to terminal
UP/DN, this function terminal can directly clear the
frequency set by UP/DN.
28
Control command switched to
keypad
If the three terminals or two of them are closed at the
same time, the priority is keypad> terminal>
29
Control command switched to