Chapter IV Function Parameter Table
56
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
41
:
Pump C maintenance signal
Note: The function assigned to different
terminals cannot be the same. If the
functions of the two terminals are set to
the same, the DI ports ranked first will
work first, and the latter ones will not
work.
Detailed description of terminal functions:
1
~
3: Forward running FWD, reverse
running REV, three-wire running control
Sin: For terminal two-wire and three-wire
control signals, see function code F6.09
description for details.
4
~
5: Forward jog and reverse jog: Used
for jog running control under terminal run
command mode, the jog running
frequency, jog interval time and jog
acceleration/deceleration time are defined
in F2.20
~
F2.23.
6: Free stop: If the function of this
terminal is valid, the drive immediately
terminates the output, and the load stops
freely according to its mechanical inertia.
7: Fault reset: When a fault alarm occurs
in the drive, the fault can be reset through
this terminal. Its function is consistent
with the STOP key function of the
keypad.
8: Running pause: If this terminal is valid
during running, the drive will decelerate
to zero frequency running according to
the deceleration time. This function is
invalid during jog running.
9: External fault input: The fault signals
of external devices can be input through
this terminal, which is convenient for the
drive to monitor the faults of external
devices. After receiving fault signals from
external devices, the drive displays
“E015”, which is the fault alarm of
external devices.
10~11: Frequency setting increase UP,
and frequency setting decrease DOWN:
The frequency increase or decrease is
realized through the control terminal, to
perform remote control replacing the
keypad. It is effective when the main
frequency F1.02 = 2 or the auxiliary
frequency F1.03 = 2, the
acceleration/deceleration rate is set by
F6.10.
12~15: Multistage speed terminals 1~4:
By selecting the terminal ON/OFF
F6.03
Function
selection
of
multi-func
tion input
terminal
DI4
12
F6.04
Function
selection
of
multi-func
tion input
terminal
DI5
13
F6.05
Multi-func
tion input
terminal
DI6
function
selection
(expansion
card)
0
F6.06
Multi-func
tion input
terminal
DI7
function
selection
(expansion
card)
0