Chapter V Basic Operation Instructions
134
Related parameter table:
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
F8.00
PID
operation
control
selection
0: Disable (Ready mode)
1: Enable (Ready mode)
1
0
×
F8.01
Target
value
channel
selection
0: F8.05 digital input;
1: AI1;
2: AI2;
3: Reserved
4: PULSE setting;
5: Communication setting
6: Multistage instruction setting
7: Keypad digital potentiometer input
8: Reserved
1
0
×
F8.02
Feedback
channel
selection
0: AI1;
1: AI2;
2: Reserved
3: Pulse
4: Communication setting
1
0
×
F8.03
Target
value
channel
filter
Set range: 0
~
1000ms
1ms
10ms
○
F8.04
Feedback
channel
filter
1ms
10ms
○
F8.05
Target
value
digital
setting
Universal drive mode setting range:
0.0
~
100.0%
Set range of professional drive mode for
water supply :
0.0
~
F8.23
0.1%
Or
0.1bar
0.0%
Or
0.0bar
○
F8.06
Proportiona
l gain Kp1 Set range: 0
~
1000
1
10
○
F8.07
Integration
time Ti1
Set range: 1
~
10000ms
1ms
500ms
○
F8.08
Differential
time Td1
Set range: 0
~
10000ms
1ms
0ms
○
F8.09
Proportiona
l gain Kp2
F8.09 set range: 0
~
1000
F8.10 set range: 1
~
10000ms
F8.11 set range: 0
~
10000ms
1
5
○
F8.10
Integration
time Ti2
1ms
2000ms
○
F8.11
Differential
time Td2
1ms
0ms
○
F8.12
Gain
switching
conditions
0: Do not switch
1: Switch through DI terminal
2: Switch automatically based on deviation
3: Switch automatically according to PID
output
1
0
○