Chapter IV Function Parameter Table
63
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
indication signal is output.
16: Drive ready to run (RDY): When the
drive has no fault, the bus voltage is
normal, and no signal is given at the drive
operation prohibition terminal, it outputs
an indication signal. In this case, the drive
indicates that the start command can be
given to the drive.
17: Drive fault: If the drive fails, an
indication is output.
18: Reserved
19: Set the accumulated running time
arrival: When the accumulated running
time of the drive (U0.27) reaches the
running cutoff time (F0.02) of the drive,
an indication signal is output.
20: Forward running indication: Outputs
an indication signal when drive is running
in forward direction.
21: Reverse running indication: Outputs
an indication signal when drive is running
in reverse direction.
22: Reserved
23: Water supply sleep indication: During
water supply application, output an
indication signal if the drive is in sleep
mode.
24: Water pipe overpressure indication:
During water supply application, output a
signal if the water pipe is in overpressure
state at any time.
25: Water pipe under-pressure indication:
During water supply application, output a
signal if the water pipe is in
under-pressure state at any time.
26:Water pipe shortage indication:
During water supply application, if the
drive finds that the water pipe is in short
of water at any time, it outputs an
indication signal.
27:Water tank shortage indication
During water supply application, if the
drive finds that the water tank is in short
of water at any time, it outputs an
indication signal.
28
:
Water pipe burst indication
During water supply application, if the
drive finds that the water pipe burst at any
time, it outputs an indication signal.